Ai 10°C to 25°C 33L/Min 35L Capacity Recirculating Chiller
Digital temperature controlled recirculating water chiller with built-in swivel casters, recommended for our IH series induction heaters. These chillers have built-in stainless steel tank, water pump and tubing for durability and rust-free operations. Water manifold included for immediate use.
Specifications
Model
WAC-4
Controller Digital micro-chip controlled with LCD screen and fluid level display
Input power 480VAC 60Hz three-phase (3PH) 3.75kW
Nominal cooling capacity 10366 kcal per hour
Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12°C
Outlet chilled fluid temperature: 7°C
Inlet cooling air temperature: 30°C
Outlet cooling air temperature: 35°C
Compressor
Make: Danfoss (UL Listed)
Power: 460V 3-60Hz 8A 3750 watts, LR 25A, thermally protected
Refrigerant: R407C (2,400g)
PS: 22.6 bar, TS max: 50°C, TS min: -35°C
Number of compressors installed: one
Water pump
Make: LX (CMF2-50T-A-W-G-BABE)
Power: 480V 60Hz 3-PH 550 watts 2.5/Y1.4A 3450 rpm IP55
Max liquid temperature: 70°C
Pumping speed: 33L per minute
Max pressure: 10 bar. H(max): 64m, H(n): 51m
Reservoir capacity 35L
Recommended coolant Distilled water
Cooling fan Make: Weiguang (YWF4D-350S-102/34-G)
Power: 480V 60Hz 80/150 watts 0.27A 1640 rpm
Number of fans installed: two
Flow rate: 142,000 cu ft per hour
Temperature accuracy +/- 2 °C
Water inlet & outlet on chiller
KF40 flange
Water manifold Inlet: KF40 flange, outlet: 8mm quick connect with ball valve
Unit/shipping weight 375 Lb / 485 Lb
Unit/shipping dimensions 41 x 22 x 54" / 50 x 25 x 61" (DxWxH)
Safety Over current, compressor delay start, water pump
over load, built-in fuse, over-voltage and under-
voltage, abnormal operations, phase protection and
Working environment Temperature range of chilled fluid: 5°C - 35°C. Temperature
difference of chilled fluid between inlet and outlet: 3°C - 8°C.
It is better to use the chiller while the ambient temperature is
at or below 35°C
Recommended to use with
these induction heaters
(result may vary on
different applications)
High frequency 10kW, 20kW, 30kW
Mid frequency 25kW, 35kW
Low frequency 25kW, 35kW
CE compliant Yes
Be the first!
Call for Pricing & Availability707-923-9319
Customer Reviews
Be the first!